DIAGNOSES — Overall System / Performance Test Diagnoses (Cont'd) — TROUBLE DIAGNOSES FOR ABNORMAL PRESSURE
HA-34spec tablePerformance Test Diagnoses (Cont'd)
TROUBLE DIAGNOSES FOR ABNORMAL PRESSURE
Whenever abnormal pressure of high and/or low sides of the system is noted, diagnosis must be conducted by using a manifold gauge. The large-line zone on the gauge scale (see illustrations.) shown in the following table refers to the standard (normal) pressure range for the corresponding pressure side (high or low). Since the standard (normal) pressure, however, differs from vehicle to vehicle, refer to the "Ambient Temperature-Pressure Characteristics" chart.
Trouble diagnoses for abnormal pressure — Case A: Both high- and low-pressure sides are too high
Both high- and low-pressure sides are too high. [A]
Refrigerant cycle• Pressure is reduced soon after water is splashed on condenser. • No air bubbles appear in sight glass when pressure is reduced.
Probable causeExcessive refrigerant charge in refrigeration cycle
Corrective actionReduce refrigerant until specified pressure is obtained.
Both high- and low-pressure sides are too high. [A]
Refrigerant cycleAir suction by radiator or condenser fan is insufficient.
Probable causeInsufficient condenser cooling performance → ① Condenser fins are clogged. ② Improper rotation of radiator fan or condenser fan
Corrective action• Clean condenser. • Check and repair radiator or condenser fan as necessary.
Both high- and low-pressure sides are too high. [A]
Refrigerant cycle• Low-pressure pipe is not cold. • When compressor is stopped high-pressure value quickly drops by approximately 196 kPa (2.0 bar, 2 kg/cm², 28 psi). It then decreases gradually thereafter.
Probable causePoor heat exchange in condenser (After compressor operation stops, high pressure decreases too slowly.) → Air in refrigeration cycle
Corrective actionEvacuate repeatedly and recharge system.
Both high- and low-pressure sides are too high. [A]
Refrigerant cycleEngine tends to overheat.
Probable causeEngine cooling systems malfunction.
Corrective actionCheck and repair each engine cooling system.
Both high- and low-pressure sides are too high. [A]
Refrigerant cycle• Areas near low-pressure pipe connection and service valves are considerably cold compared with areas near expansion valve outlet or evaporator. • Plates are sometimes covered with frost.
Probable cause• Excessive liquid refrigerant on low-pressure side • Excessive refrigerant discharge flow • Expansion valve is open a little compared with the specification. → ① Improper thermal valve installation ② Improper expansion valve adjustment
Corrective actionReplace expansion valve.
See also
Ambient Temperature-Pressure Characteristics chart